BS 6004
PVC insulated, PVC sheathed, flat cables
Used as surface wiring where there is little mechanical damage risk, or in conduit.
Nominal cross
(mm²) |
Outside diameter
(Yaklaşık mm²)
|
Net weight
(kg/km)
|
Conductor D.C. resistance
(20°C | ohm/km) |
Current carrying capacity in |
| Conduit (20°C (A) |
| 6192Y (300/500 V) |
| 2 x 1 re |
4,1 x 6,4 |
49,5 |
18,1 |
13 |
| 2 x 1,5 re |
4,7 x 7,6 |
70,0 |
12,1 |
16 |
| 2 x 2,5 re |
5,6 x 9,2 |
105,0 |
7,41 |
21 |
| 2 x 4 rm |
6,1 x 10,2 |
139,0 |
4,61 |
27 |
| 2 x 6 rm |
6,9 x 1 1 ,6 |
187,0 |
3,08 |
34 |
| 2 x 10 rm |
8,3 x 14,2 |
298,0 |
1,83 |
45 |
| 2 x 16 rm |
9,4 x 16,2 |
425,0 |
1,15 |
57 |
| 6193Y (300/500 V) |
| 3 x 1 re |
4,1 x 8,7 |
71,0 |
18,1 |
13 |
| 3 x 1,5 re |
4,6 x 10,2 |
98,0 |
12,1 |
16 |
| 3 x 2,5 re |
5,4 x 12,2 |
146,0 |
7,41 |
21 |
| 3 x 4 rm |
6,3 x 14,5 |
210,0 |
4,61 |
27 |
| 3 x 6 rm |
6,9 x 16,3 |
277,0 |
3,08 |
34 |
| 3 x 10 rm |
8,3 x 20,1 |
442,0 |
1,83 |
45 |
| 3 x 16 rm |
9,4 x 23,0 |
633,0 |
1,15 |
57 |
| (re: Solid , rm: Rijit) |